LST Home Security System M500RFE AS User Manual

RF Interface  
M500RFE-AS  
• ADM loop technology with  
System Sensor/200 protocol  
• Up to 99 automatic detectors and 98  
manual call points can be controlled  
• Multi-language operating menu  
• High range of radio transmission  
• Two frequency bands (868/434MHz)  
with automatic change-over  
• Channel checked for availability  
Description  
The RF Interface M500RFE-AS serves as a gateway means of the automatic learning process. A manual pa-  
between radio detectors and a Fire Detection Control rameterisation is also possible.  
Panel Series BC216. The communication with the con- The RF interface is operated and configured using  
trol panel is established via the ADM loop with System the built-in key pad and the alphanumeric display. The  
Sensor/200 protocol.  
multi-language operating menu serves for the parame-  
terisation as well as for displaying the signal strength  
The RF interface can communicate with up to 99 auto- of any individual detector. A 6-digit authorisation code  
matic radio detectors and up to 98 manual radio call provides protection against unauthorised access. Three  
points. For each automatic radio detector one detector LEDs indicate the interface conditions operation, alarm  
is parameterised in the fire detection control panel, and and fault.  
for each manual radio call point one module is para-  
meterised. The gateway itself occupies one module The RF interface is designed for indoor surface moun-  
address on the loop.  
ting and is equipped with a dual-isolator, which discon-  
The detectors are configured at the RF interface by nects the loop in case of a short circuit.  
Specifications  
Operating voltage  
10 – 30VDC  
Current consumption external supply (at 24V)  
Current consumption from loop  
Range of radio transmission (free air)  
Frequency band  
max. 80mA  
325µA (quiescent)  
300m  
868MHz or 434MHz  
-10°C to +55°C  
210 × 270 × 70 (mm)  
white/black  
Ambient temperature  
Dimensions W × H × D  
Colour  
Weight  
930g  
Approval  
VdS G208132  
249202  
Order number  
Order name  
RF Interface/Anal./SS M500RFE-AS  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
M500RFE-AS_DBL_LST_EN_0906.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

Land Pride Lawn Mower FDR35 User Manual
Land Pride Spreader FSP1000 User Manual
Lenovo Computer Drive 41N5631 User Manual
Liebert Stereo System TM 10098 User Manual
Lindy Computer Monitor 70541 User Manual
Makita Impact Driver 6952 User Manual
Mark Levinson Stereo Amplifier No 33H User Manual
Marvel Group Refrigerator 6GARM User Manual
Maytag Range 8113P644 60 User Manual
MGE UPS Systems Power Supply Galaxy PW User Manual